Advance's rule of thumb
| Model | Output | Nominal heat output | Radiators | Typical home |
|---|---|---|---|---|
| EG 6 | 6kW | 20,000 BTU | 4 or 5 | 1 or 2 bed apartment |
| EG 9 | 9kW | 30,000 BTU | 6 or 7 | 2 bed house |
| EG 12 | 12kW | 40,000 BTU | 8 or 9 | 3 bed house |
Advance Appliances says these counts depend on radiator size, so it has averaged them out. Treat them as a starting point.
Size it on the heating demand
The Eglow installation guide asks installers to calculate the space heating requirement and size the boiler to meet it. Match the boiler's output to that figure rather than counting radiators.
If the Eglow will also heat an indirect hot water cylinder, the guide says to allow an extra 3kW. A home needing 6kW for its radiators would then need the 9kW model.
Pipework and controls
- Use a twin pipe 22mm system with 15mm tees to the radiators.
- Keep one radiator or towel rail locked open, and put the room thermostat in that room.
- Thermostatic valves on the other radiators are recommended.
- Fit a programmer and room thermostat to meet Part L of the Building Regulations.
The Eglow only runs on a sealed system. The sealed system kit has an 8 litre expansion vessel, and the guide warns that systems holding a lot of water may need a larger one.
Check the electricity supply
More radiators means a bigger boiler and a bigger current draw: 30 amps for the 6kW, 40 for the 9kW and 50 for the 12kW, protected at 32, 45 and 63 amps. The guide says the full house loading must be taken into account.
More radiators than one Eglow can run
If an extension adds radiators to an existing gas or electric system, Advance suggests boosting it with a Plug N Glow 2, which runs a couple of radiators, in place of changing the boiler.
On a self build in Morayshire with no gas supply, Rob Rankin paired a 12kW Eglow with an Advance multi fuel thermal store and a wood burner. He said of Advance: "Their response has been great – and happily all is now working fine." See how that works in thermal stores with a wood burner.
- The 6kW Eglow runs four or five radiators, the 9kW six or seven and the 12kW eight or nine.
- These are Advance's averages; radiator size changes the answer.
- Size the boiler on the total radiator output, and add 3kW if it also heats an indirect cylinder.
- The 6, 9 and 12kW models draw 30, 40 and 50 amps, so check the household supply.
- To add radiators after an extension, a Plug N Glow can boost the existing system.