What does a buffer store do?

  • Buffer Stores
  • 3 min read
  • Updated 7th October, 2026
answer

A buffer store holds heated water from a low or intermittent heat source, such as a heat pump, so the energy is there when the heating calls for it. It also adds volume to the primary circuit and gives the heat pump a low temperature return, which stops it switching on and off too often, known as short cycling. A buffer can also store heat from a wood burner or biomass boiler, acting as an energy accumulator.

What short cycling is

Short cycling is a heat pump starting and stopping its compressor too often. Kensa Heat Pumps, a UK ground source heat pump maker, says a ground source heat pump "achieves a higher efficiency when it doesn't have to keep stopping and starting its compressor too frequently", and that short cycling can cause premature wear and tear.

A 2013 laboratory study for the Department of Energy and Climate Change recorded cycles as short as about 11 minutes, or 5.4 starts an hour, against the 3 to 4 starts an hour it cites as recommended. It found buffers matter most with fixed speed heat pumps, especially air source, and less with inverter driven ones that can turn down to about 30% of their rated output.

A buffer keeps the heat pump's minimum flow

A buffer adds water to the heating circuit. As radiator valves and underfloor actuators close, they restrict flow around the system. Kensa calls the buffer "essentially an uncontrolled part of the system", doing the job an automatic bypass valve would do on a traditional system, so the heat pump keeps its minimum flow.

Advance Appliances' data sheet adds a second use. Buffers are mainly fitted with heat pumps, but they can also store heat from wood burners and biomass boilers as accumulators. If you want one store to take a wood burner, solar and a boiler and give hot water too, see the multi fuel thermal store instead.

How a buffer connects

Advance's stainless steel buffers have four tappings: two take heat from the heat pump and two feed the heating circuit, with the top and bottom tappings as flow and return. The installation guide notes that not all heat pumps connect this way, so always follow the heat pump maker's instructions. All buffers can be set up as two port or four port systems.

The 20 litre buffer is different. It has two connections, no immersion heater, and is for adding volume only.

The Advance range

Model Capacity Material Immersion Guarantee
BFS 20 20 litres Mild steel, wall hung None 2 years
AA BFS 100 100 litres Mild steel, box shaped 1 x 3kW 2 years
ECO BFS 150 to 300 150 to 300 litres Duplex stainless steel 1 x 3kW 25 years

Larger stainless sizes up to 500 litres are on the data sheet; call Advance on 01543 377723 about those. The stainless buffers work up to 3 bar and 95°C, are approved by WRAS (the Water Regulations Advisory Scheme) and fully recyclable, and the 150 to 300 litre models are A rated for heat loss.

Whether your system needs one at all is a separate question: see do I need a buffer store with my heat pump.

key takeaways
  • A buffer store adds water to a heat pump's heating circuit so the compressor does not start and stop too often.
  • Buffers matter most with fixed speed heat pumps, especially air source, according to a 2013 study for DECC.
  • Buffers can also store heat from wood burners and biomass boilers as accumulators.
  • Advance stainless buffers have four tappings; the 20 litre has two and is for adding volume only.
  • Advance makes mild steel buffers of 20 and 100 litres and stainless steel buffers from 150 litres.

Reviewed by Geoff Egginton

Managing Director, Advance Appliances. 20+ Years experience